Description
Specifications
| Air Flow CFM (L/S) |
|||
| 0 | 0.2 | 0.3 | 0.4 |
| 320 (151) |
292 (137) |
253 (119) |
231 (109) |
| Size LxHxD | Weight |
| in (mm) | lb (kg) |
| 36 x 23 x 17 (914 x 584 x 432) |
50 (22.7) |
|
Core
|
Duct Size |
Defrost Type
|
Effectiveness
Sensible |
| in (mm) | |||
| Polypropylene | 8 (203) |
FSD or Damper Circulation | 66-70% |
Controls
![]()
- 24V dry contacts available for 2-speed control, time-clocks, occupancy and CO sensors also available.
- For units up to NU1600, ES Series controls are available.
Defrost Strategies (-5°C/23°F and colder)
- Fan Shut Down: Supply fan shuts down while the exhaust fan continues to move warm air through the core.
- Damper: A damper closes the OA port and opens a fifth port which brings warm air through the core for a predefined time cycle. The exhaust fan remains on.
Commercial Heat & Energy Recovery Ventilators
- Nu-Air Commercial HRV’s/ERV’s provide fresh air to conditioned spaces while simultaneously exhausting stale air through a cross-flow heat exchanger where energy is transferred from the exhaust to supply air without cross contamination.
- Polypropylene Cores: Sensible temperature effectiveness averages 65-75% in heating season and 20 – 30% in cooling season
- Enthalpy Cores: Sensible temperature effectiveness averages 60-80% in heating season and 50 – 70% in cooling season.
- These efficiencies enable the downsizing of mechanical systems and reduce capital and operating costs.
Certifications
- Allunits, unless noted, listed to CSA Std. 22.2 No. 113 and conform to UL Std. 1812.
- *NU2200 conforms to CSA SPE1000


Standard Features (units up to NU1600)
- Forward curve DWDI blowers
- Permanently sealed bearings
- Temperature activated fan shut down defrost
- 1″ pleated filters 30-40% ASHRAE dust spot efficiency
- Remote or automatic controls and sensors
- Condensate drain and anti-vibration kits included
- Large surface area heat recovery cores
WARRANTY
- Nu-Air warrants its Commercial polypropylene HRV cores to be free from defects for a period of 15 years. There is a five (5) year warranty on ERV (latent) cores.
- Light Commercial and Compliant Series HRV’s have a two (2) year warranty on all electrical components including motors, circuit boards, transformers, switches, etc.